  data sheet august 2009 compact power line cp2000ac54 front-end power supply input: 100-120/200-240 vac; outputs: 54 vdc at 2000w; 5 vdc at 4w applications ? 48vdc distributed power architectures ? power over ethernet ? routers/switches ? voip/soft switches ? lan/wan/man applications ? file servers ? indoor wireless ? telecommunications equipment ? enterprise networks ? san/nas/iscsi applications ? advanced workstations features ? compact 1-ru form factor providing 20 w/in3 ? constant power from 52 ? 58 vdc ? 2000w from nominal 200 ? 240 vac ? 1200w from nominal 100 ? 120 vac ? output voltage programmable from 44v ? 58 vdc; output defaulted to 54v ? pmbus compliant dual i 2 c and rs485 serial bus communications ? power factor correction (meets en/iec 61000-3-2 and en 60555-2 requirements) ? tested to ieee802.3 compliance, 2250 output*** isolation to chassis/signals for poe applications. (see ordering info) ? dc output over-voltage and over-current protection ? ac input over-voltage an d under-voltage protection ? over-temperature warning and protection ? redundant, parallel operation with active load sharing and redundant +5v aux power ? remote on/off ? hot insertion/removal (hot plug) ? four front panel led indicators ? ul* recognized to ul60950-1, can/ csa ? c22.2 no. 60950-1, and vde ? 0805-1 licensed to iec60950-1 ? ce mark meets 2006/95/ec directive ? internal variable-speed fan control the cp2000ac54 front-end power supplies in the compact power line platform are specifically designed to operate as an integral part of a complete distributed power system. the high-density, front-to- back airflow rectifier is designed for minimal space util ization and is highly expandable for future growth. it is provided with many features including poe isolation, rs485 and dual-redundant i 2 c communications busses that allow it to be used in a broad range of ap plications. the flexible f eature set makes this front- end power supply an excellent choice for applications requiring modular ac-to-dc bulk intermediate voltages, such as in distributed power. * ul is a registered trademark of underwriters laboratories, inc. ? csa is a registered trademark of canadian standards association. ? vde is a trademark of verband deutscher elektrotechniker e.v. this product is intended for integration into end-user equipm ent. all the required procedures for ce marking of end-user equipment should be followed. (the ce ma rk is placed on selected products.) ** iso is a registered trademark of the international organization of standards. *** for poe applications, order the CP2000AC54PEz, wh ich is 100% factory hipot-tested per ieee802.3.
data sheet compact power line cp2000ac54 front-end power supply lineage power 2 specifications input parameter min typ max units notes startup input voltage 1200w operation 2000w operation operating voltage range 1200w configuration 2000w configuration 2000w configuration permitted excursions surges 85 175 150 275 300 120/200/240 200/240 85 175 275 275 175 300 325 vac the power supply automatically configures its operating mode based on the voltage level it reads on first turn on. (this information is retained as long as intern al bias is maintained.) if started within low input line range. if started within high input line range. will derate to 80% of full load; will shutdown below 150vac. may not meet all requirements, but will maintain output regulation. may shut down but will not get damaged. input frequency 47 63 hz input current 13.3 11.2 11.8 9.9 a at 100 vac at 120 vac at 200 vac at 240 vac inrush transient 25 35 apk measured at 25c for all line conditions; does not include x-capacitors charging. input leakage current 1.5 ma measured at 265vac, 60hz power factor 0.98 from 50% to 100% load. efficiency 85 88 90 93 % at 100 vac with vout > 52v and pout > 50%. at 230 vac with vout > 52v and pout > 50%. holdup time 15 20 ms measurement starts at zero crossing of the ac voltage. alarm issued via pfw signal going lo 5 ms prior to output voltages going out of limits. measurements made at 65% full load and voltage allowed to decay to 49.5v. for loads below 1200w. main output parameter min typ max units notes maximum output power 1200 2000 w at low-line input from 100-120vac nominal. at high-line input from 200-240vac nominal. output voltage setpoint 54 vdc output floats with respect to frame ground. setpoint accuracy -1 +1 % overall regulation -2 +2 % includes all variations due to specified load range, drift, and environmental conditions. 44 58 vdc configured by hardware setting. output voltage margin 42 58 vdc set either by i 2 c or rs485 maximum output current 23 38.5 a at 1200w, 52v and 100-120vac. at 2000w, 52v and 200-240vac. current share 10 %fl maintains tolerance to the average of all other rectifiers. loads > 25%fl
data sheet compact power line cp2000ac54 front-end power supply lineage power 3 specifications (continued) output (continued) parameter min typ max units notes output ripple rms (5hz to 20mhz) peak-to-peak (5hz to 20mhz) psophometric noise 250 500 2 mvrms mvpk-pk mvrms measured with 20mhz bandwidth under any condition of loading. minimum load is 1a. external bulk load capacitance 0 5,000 f external capacitance can be increased but the power supply will not meet its turn-on rise time requirement. turn-on delay rise time 1 - standard (pmbus) -telecom (rs-485) 2 overshoot 5 100 5 2 s ms s % monotonic turn_on from 30% to 100% of vnom above -5c operation. monotonic turn_on from 60% to 100% of vnom below -5c operation. load step response ? i ? v response time 2.0 2 50 %fl vdc ms ? i/ ? t slew rate 1a/s. settling time to within regulation requirements. overload power limit current limit inception 3 2000 102 108 w %fl down to -52vdc hiccup current limit. (fl = 38.5a) 60 65 vdc vdc 200msec delayed shutdown to be implemented. instantaneous shutdown above this point. over-voltage delayed immediate latchoff three restart attempts may be implemented within a one minute window prior to a latched shutdown 20 5 c c implemented prior to commencement of an ot shutdown below the maximum rating of the device being protected over-temperature warning shutdown auto-recoverable temperature hysteresis of approximately 10c provided between shutdown and restart. 1. below -5c, the rise time is approximate ly 5 minutes to protect the bulk capacitors. 2. complies with gr947 which calls for a minimum rise time proportional to output load. 3. fold-down current limit is programmed as a default to permi t system start-up when units are plugged in one at a time. latch- off mode current limit can be activated via an i2c command. auxiliary output parameter min typ max units notes output voltage setpoint 5 vdc output current 0.005 0.75 a overall regulation -5 +10 % ripple and noise 50 100 mvpk-pk 20mhz bandwidth over-voltage clamp 7 vdc over-current limit 110 175 %fl physical length (in./mm) 13.85 / 351.8 width (in./mm) 4.00 / 101.6 height (in./mm) 1.66 / 42.2 weight (lb/kg) 4.6 / 2.1
data sheet compact power line cp2000ac54 front-end power supply lineage power 4 specifications (continued) environmental parameter min typ max units notes ambient temperature operating ambient derating power derating 2 -5 1 1 45 1 2 c c %/c %/c air inlet from sea level to 5,000 feet. per 1,000 feet above 5,000 feet. up to 55c from 55 to 75 c storage temperature -40 85 c humidity 5 95 % relative humidity, non-condensing shock and vibration operational test test levels drop and tip over iec 68-2 iec 721-3-2 iec 68-2-31 earthquake rating 4 zone per telcordia gr-63-core, all floors, when installed in cp shelf. acoustic noise 45 dba noise is proportional to fan speed, load and ambient temperature. harmonic emissions per en/iec61000-3-2 radiated emissions 4 fcc and cispr22 (en55022) - class b 3 conducted emissions - ac fcc and cispr22 (en55022) class b telcordia gr-1089-core - class a conducted emissions - dc te lcordia gr-1089-core and cispr22 (en55022) - class a esd error free per en/iec 61000-4-2 level 4 (8 kv contact discharge, 15 kv air discharge). radiated immunity error free per en/iec 61000-4-3 level 3 (10 v/m). electrical fast transient burst error free per en/iec 61000-4-4 level 3 (2 kv, 5 khz repetition rate) lightning surge error free damage free en/iec61000-4-5 level 4 (4 kv common mode, 2 kv differential mode). ansi c62.41 level a3 (6 kv common and differential mode) conducted immunity error free per en/iec 61000-4-6 level 3 (10vrms). reliability (calculated) 400,000 hours at ambient of 25c at full load per telcordia sr- 332, reliability prediction for electronic equipment, method i case iii. isolation input-chassis/signals input - output output-chassis/signals 1500 3000 2250 vrms vrms vdc per en60950-1. consult factory for testing to this requirement per ieee802.3. service life 10 years 25c ambient, full load excluding fans. 1. designed to start at an ambient as low as -40c, but may not meet operational limits until above -5c. 2. power derating shall consider only te mperature variations at nominal line ( 100 ? 120, 200 ? 240vrms). the unit may derate faster if the input line is below nominal. 3. class b radiated emmissions compliance re quires the addition of a ferrite bead to eac h power line cord at the shelf-end of t he cable. see the figure below. 4. radiated emissions compliance was met using a lineage power shelf. th is shelf includes output common and differential mode capacitors that assist in meeting compliance.
data sheet compact power line cp2000ac54 front-end power supply lineage power 5 status and control the rectifier provides three means for monitor/control: analog, pmbus compliant i 2 c, or rs485 for interfacing to lineage power controllers or battery plants. details of analog controls are provided in this data sheet under signal definitions. lineage power will provide separate application notes on pmbus protocol for users to interface to the cpl rectifiers. contact your local lineage power representative for details. hot plug when rapidly extracting and reinserting modules care should be taken to allow for discharging the internal bias supply so that a predictable restart could be achieved. the way to ensure that the circuit sufficiently discharges is to observe the spinning of the fans after an extraction. the unit should not be reinserted until the fans stop spinning. control definitions all signals are referenced to logic grd unless otherwise noted. see the signal definitions table at the end of this document for further description of all the signals. input signals margining: setpoint of the rectifier can be changed via this input pin. programming can be either a voltage source or a resistance divider. the margining pin is connected to 3.3vdc via a 10k ? resistor inside the rectifier. see graphs below. an open circuit on this pin reverts the voltage level back to the original setting. module present signal: this signal has dual functionality. it can be used to alert the system when a module is inserted. has a 500 ? resistor in series between this signal and logic grd. an external pull-up should not raise the voltage on the pin above 0.25vdc. if raised the pin is raised to 5vdc the write_protect feature of the eeprom is enabled. protocol select: establishes the communications mode of the power supply, between analog/i 2 c and rs485 modes. for rs485, connect 750 ? 3.92k ? pull-down resistor to 54_out(-dc). enable: on/off control when either pmbus communications or analog functions are utilized as configured by the protocol pin. this pin must be pulled low to turn on the main output of the power supply. the power supply will turn off if either the enable or the on/off pin is released. the enable function does not work with the rs-485 protocol. this signal is referenced to logic_grd. on/off: this is a short pin utilized for hot-plug applications to ensure that the power supply turns off before the power pins are disengaged. it also ensures that the power supply turns on only after the power pins have been engaged. must be connected to 54_out (-dc). output signals alert #: pmbus interrupt signal. fault: this signal goes lo for any failure that requires rectifier replacement. some of these faults may be due to: ? fan failure ? over-temperature condition ? over-temperature shutdown ? over-voltage shutdown ? internal rectifier fault power capacity: a hi on this pin indicates rectifier configured for 2000w operation; a lo indicates rectifier configured for 1200w operation.
data sheet compact power line cp2000ac54 front-end power supply lineage power 6 alarm table power supply led state monitoring signals (referenced to logic_grd) condition ac ok green dc ok green service amber fault red fault otw pfw module present ok 1 1 0 0 hi hi hi lo thermal alarm (5c before shutdown) 1 1 1 0 hi lo hi lo thermal shutdown 1 0 1 1 lo lo lo lo defective fan 1 0 0 1 lo hi lo lo blown ac fuse in unit 1 0 0 1 lo hi lo lo no ac <15ms (single unit) 0 1 0 0 hi hi lo 3 lo ac present but not within limits blinks 0 0 0 hi hi lo lo ac not present 1 0 0 0 0 hi hi lo lo boost stage failure 1 0 0 1 lo hi lo lo over voltage latched shutdown 1 0 0 1 lo hi lo lo over current 1 blinks 0 0 hi hi lo lo non-catastrophic internal failure 2 1 1 0 1 lo hi hi lo 1 missing module hi standby (remote) 1 0 0 0 hi hi lo lo service request (pmbus mode) 1 1 blinks 0 hi hi hi lo communications fault (rs485 mode) 1 1 0 blinks hi hi hi lo 1 this signal is correct if the rectifier is back biased from other rectifiers in the shelf . 2 any detectable fault condition that does not result in the pow er supply shutting down. for ex ample, oring fet failure, boost section out of regulation, etc. 3 signal transition from hi to lo is output load dependent output connector mating connector: amp 1450572-1 p1 a6 p7 a1 signal output power input power 6 5 4 3 2 1 p7 p6 p5 p4 p3 p2 p1 a scl_0 mod_pres pfw logic_grd rs_485+ unit_addr b scl_1 otw alert#_0 alert#_1 rs_485- 8v_int c sda_0 margin enable reset ishare protocol d sda_1 fault 5va power_cap on/off shelf_addr 54_out (-dc) 54_out (+dc) reserved earth (gnd) line-2 (neutral) line-1 (line) connector is viewed from the rear positioned inside the power supply. signal pins columns 1 and 2 are referenced to 54_out (-dc). signal pins columns 3 through 6 are referenced to logic grd. last-to-make first-to-break pins. first-to-make last-to-break longest pi n implemented in the mating connector.
data sheet compact power line cp2000ac54 front-end power supply lineage power 7 signal definitions all hardware alarm signals (fault, pfw, otw, po wer capacity) are open drain fets. these signals should be pulled hi to either 3.3v or 5v. maximum sink current 5ma. an active lo signal (< 0.4vdc). all signals are referenced to logic grd unless otherwise stated. contact your lineage power representative for more details. function label type description output enable enable input if shorted to logic_grd, the rectifier output is enabled when using i 2 c mode of operation. may also be toggled to reset a latched off rectifier. function not available in rs485 mode. power fail warning pfw output an open drain fet; normally hi, indicating output power is present. changes to lo at least 5msec before the output voltage is lost. i 2 c interrupt alert#_0 alert#_1 output interrupt signal via i 2 c lines indicating that service is requested from the host controlle r. this signal pin is pulled up to 3.3v via a 10k ? resistor and switches to active lo when an interrupt occurs. rectifier fault fault output i ndicates that an internal fault exists. an open drain fet; normally hi, changes to lo. module present mod_pres output short pin, se e status and control description for further information on this signal. on/off on/off input short pin, connects last and breaks first; used to activate and deactivate output during hot-insertion and extraction, respectively. ref: 54_out (-dc) protocol select protocol input see status and control description for further information on this signal. ref: 54_out (-dc). margining margin input allows changi ng of output voltage through an analog voltage input or via resistor divider. over-temperature warning otw output an ope n drain fet; normally hi, changes to lo approximately 5c prior to thermal shutdown. power capacity power_cap output an open drai n fet; used to indicate rectifier operation mode; hi indicates 2000w operation and lo indicates 1200w operation. rectifier address unit_addr input voltage level addressing of rectifiers within a single shelf. ref: 54_out (-dc). shelf address shelf_addr input voltage level addressing of rectifiers within multiple shelves. ref: 54_out (-dc). back bias 8v_int _ diode or?ed 8vdc drain; used to back bias microprocessors and dsp of failed rectifier from operating rectifiers. ref: 54_out (-dc). mux reset reset input resets the i 2 c lines to i 2 c line 0. standby power 5va output 5v at 0.75a prov ided for external use by either adjacent power supplies or the using system. current share ishare - a single wire inte rface between each of the power unit forces them to share the load current. ref: 54_out (-dc). i 2 c line 0 scl_0, sda_0 input i 2 c line 0. i 2 c line 1 scl_1, sda_1 input i 2 c line 1. rs485 line rs_485+ rs_485- input rs485 line.
data sheet compact power line cp2000ac54 front-end power supply lineage power page 8 world wide headquarters lineage power llc 601 shiloh road, plano, tx 75074, usa +1-800-526-7819 (outside u.s.a.: +1-972-284-2626 ) www.lineagepower.com e-mail: techsupport1@lineagepower.com asia-pacific headquarters tel: +65 6593 7211 europe, middle-east and africa headquarters tel: +49 898 780 672 80 india headquarters tel: +91 80 2841 1633 lineage power reserves the right to make changes to the product(s) or information contained herein without notice. no liability is assumed as a result of their use or application. no rights under any patent accompany the sale of any such product(s) or information. ? 2009 lineage power llc, (mesquite, texas) all international rights reserved. revision : ggs-august 2009 front panel leds analog mode i 2 c mode rs485 mode on: input ok blinking: input out of limits on: output ok blinking: overload on: over-temperature warning on: over-temperature warning blinking: service on: over-temperature warning ! on: fault blinking: not communicating dimensions 13.85 in. (351.8 mm) 4.00 in. (101.6 mm) 1.70 in. (43.2 mm) rear v iew front view top view ordering information item description comcode CP2000AC54PE designed to ieee802.3 poe compliance, rohs 5/6 cc109120722 CP2000AC54PEz tested to ieee802.3 po e compliance, rohs 6/6 cc109139408 on: fault


▲Up To Search▲   

 
Price & Availability of CP2000AC54PE

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X